1Model 5000 Electronic Air CleanerInstallation InstructionsWARNING120 Volts may cause serious injury from electrical shock. Disconnect power to the fu
10Inner HousingIonizer FrameControlElectrodeControl ElectrodeIonizer FrameControlElectrodeGroundContactMedia GroundContactsIonizerWiresBus BarFIGURE 1
11APPLICATIONS WITH A HUMIDIFIERAn Aprilaire® Automatic Humidifier can be mounted upstream from the air cleaner. CAUTIONDo not install an atomizing hu
P.O. Box 1467 • Madison, WI 53701-1467 • Phone: 800/334-6011 • Fax: 608/257-4357 • www.aprilairepartners.com10007971 2.14B2701048BPrinted in U.S.A.©
231" with Door28-1/8" without Door12"24-5/8"23-7/8"15-1/2"17-3/4"18-3/8"15-1/2"FIGURE 1 – Dimensions of t
3Pleat Spacers (6)#501 MediaOuter Housing with Door RetainersInner Housing AssemblyInner HousingIonizer FrameControl ElectrodePower Pack/Door Assembly
4LOCATING THE AIR CLEANERAirflow Airflow Airflow Airflow 30 max. 45 max. Minimize Angles Where PossibleAirflow Plenum Box Airflow Plenum Box Size Plen
5 1. Turn the system OFF at the thermostat by changing the mode selector to OFF – this may be a switch or a pushbutton, depending on the type of ther
6WIRING AND START UP 1. Install a grounded (earth ground) 120-volt single receptacle outlet in accordance with NEC Standards and local codes, into w
7EACNEUTRALGNDHVAC Equipment Control Center Circuit BoardIT IS COMMON TO SEE SPADE TERMINALS ON THE HVAC EQUIPMENT CONTROL CENTER CIRCUIT BOARD. USE
8TROUBLESHOOTING GUIDEPROBLEM POSSIBLE CAUSE(S) SOLUTION(S)Light does not come on at all after 90 secondsON/OFF switch not in ON position Turn switch
9MAINTENANCE RECOMMENDATIONSWhenever performing maintenance on the air cleaner, turn off the HVAC system, then turn off and unplug the air cleaner. B